EasyManua.ls Logo

Delta AH500 - Page 285

Delta AH500
681 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
AH500 Hardware and Operation Manual
4-118
A bulb (incandescent lamp) is used as a DC load. A thermistor is connected in series to absorb the
surge current which occurs when the load is ON.
Y0.9 can not be connected to a power supply directly. It must be connected to a load.
Mutually exclusive output: For example, Y0.10 controls the clockwise rotation of the motor, and Y0.11
controls the counterclockwise rotation of the motor. The interlock circuit which is formed, and the
program in the PLC ensure that there are protective measures if an abnormal condition occurs.

Table of Contents

Other manuals for Delta AH500

Related product manuals