Chapter 12 Troubleshooting
12-29
Error
Code
Description Solution
16#600C
The communication socket has
been used. (SM1109)
1. Check whether the actual data access results in the
use of the same socket.
2. Change the socket number, or retry the socket later.
(This error does not cause the PLC to stop running.
Users can perform the corresponding remedy by
means of the related flag in the program.)
16#600D
The RJ45 port is not connected.
Check the communication cable.
16#600E
An RJ45 port on AH10EN-5A is not
connected to a network cable.
Please check whether AH10EN-5A is connected to a
network cable.
16#6100
The email connection is busy.
(SM1113)
Retry the email connection later. (This error does not
cause the PLC to stop running. Users can perform the
corresponding remedy by means of the related flag in
the program.)
16#6104
The attachment in the email does
not exist. (SM1113)
Check whether the attachment exists in the memory
card.
16#6105
The attachment in the email is
oversized. (SM1113)
Check the size of the file which is specified as the
attachment. If the size is over 2 MB, the file can not be
specified as the attachment.
16#6107
There is an SMTP server response
timeout. (SM1113)
1. Check whether the status of the SMTP server is
normal.
2. Retry the sending of the email later. (This error does
not cause the PLC to stop running. Users can perform
the corresponding remedy by means of the related
flag in the program.)
16#6201
The local communication port set
in the TCP socket function is
illegal.
1. Check the program and the related special data
registers.
2. Set the Ethernet parameter for the CPU module in
HWCONFIG again.
16#6202
The remote communication port
set in the TCP socket function is
illegal.
1. Check the program and the related special data
registers.
2. Set the Ethernet parameter for the CPU module in
HWCONFIG again.
16#6203
The device from which the data is
sent in the TCP socket function is
illegal.
1. Check the program and the related special data
registers.
2. Set the Ethernet parameter for the CPU module in
HWCONFIG again.
16#6204
The transmitted data length set in
the TCP socket function is illegal.
1. Check the program and the related special data
registers.
2. Set the Ethernet parameter for the CPU module in
HWCONFIG again.
16#6205
The data which is sent through the
TCP socket exceeds the device
range.
1. Check the program and the related special data
registers.
2. Set the Ethernet parameter for the CPU module in
HWCONFIG again.
16#6206
The device which receives the data
in the TCP socket function is
illegal.
1. Check the program and the related special data
registers.
2. Set the Ethernet parameter for the CPU module in
HWCONFIG again.
16#6207
The received data length set in the
TCP socket function is illegal.
1. Check the program and the related special data
registers.
2. Set the Ethernet parameter for the CPU module in
HWCONFIG again.