Chapter 12 Troubleshooting
12-31
Error
Code
Description Solution
16#6219
The data is being received through
Check whether operational sequence in the program is
16#621A The socket is closing.
Check whether operational sequence in the program is
16#6303
The remote device in the Ether
Link aborts the connection.
1. Check the connection and the status of the remote
device.
2. Check whether the remote device supports the Ether
16#6304
The connection in the Ether Link is
busy.
1. Check whether the number of connections in the
Ether Link exceeds the system load.
2. Retry the connection in the Ether Link later.
16#6309
The remote device in the Ether
Link does not respond after the
timeout period.
1. Check whether the CPU module in the Ether Link
operates normally.
2. Check whether the CPU modules are connected
16#6400
The number of TCP connections
reaches the upper limit, or the flag
which is related to the sending of
the data is not set to ON.
1. Check whether the flag which is related to the sending
of the data in the program is modified.
2. Retry the setting of the flag and the sending of the
packet.
16#6401
The remote device aborts the
Check whether the remote device support the Modbus
16#6402
There is no response from the
remote device after the timeout
Check whether the remote device operate normally.
16#6403
The remote IP address is illegal.
Check whether the program is correct.
16#6404
The function code is NOT
Check the command transmitted from the remote
16#6405
The number of data received is not
consistent with the actual length of
Check the command transmitted from the remote
device.
16#6501
The remote device involved in the
data exchange does not respond
after the timeout period.
Check the device whose connection number
corresponds to the error flag, and check whether it is
connected normally.
16#6502
The remote device involved in the
data exchange does not respond
Check the device whose connection number
corresponds to the error flag, and check whether it is
16#6600
The network number which
receives the command exceeds
Check the command transmitted from the remote
device.
16#6601
The network is undefined in the
network configuration parameter.
Check the network configuration in NWCONFIG, and
16#6604
The number of routing connections
reaches the upper limit.
Resend the packet later. ((This error does not cause the
PLC to stop running. Users can perform the
corresponding remedy by means of the related flag in
16#6605
The unexpected packet is
Check the command transmitted from the remote