Chapter 12  Troubleshooting 
12-51 
Description  Remedy 
16#A019 
binary-coded decimal number is 
Modify the operation to prevent the abnormal number 
from occurring. 
16#A01A 
Incorrect division operation (The 
Modify the operation to prevent the divisor from being 
Modify the program to make the syntax correct. 
16#A01C 
LD/LDI has been used more than 
Modify the program to prevent LD/LDI from being used 
16#A01D 
There is more than one level of 
nested program structure supported 
Modify the program to prevent more than one level of 
nested program structure supported by RPT/RPE from 
16#A01E 
SRET is used between RPT and 
Modify the program to prevent SRET from being used 
16#A01F 
There is no M102 in the main 
program, or there is no M2 in the 
Modify the program so that there is M102 in the main 
program, or modify the program so that there is M2 in 
16#A020 
The wrong instruction is used, or the 
device used exceeds the range. 
Check and modify the program to prevent the wrong 
instruction from being used, or check whether the 
device used exceeds the device range.