CAUTION: In North America, AC power cords must not exceed approximately 14.75 ft
(4.5 m) in length, to comply with National Electrical Code (NEC) Sections 400-8 (NFPA
75, 5-2.2) and 210-52, and Canadian Electrical Code (CEC) Section 4-010(3). The cords
supplied with the router are in compliance.
CAUTION: The router is pluggable type A equipment installed in a restricted-access
location. It has a separate protective earthing terminal (sized for UNC 1/4-20 ground
lugs) provided on the chassis in addition to the grounding pin on the power cord. This
separate protective earthing terminal must be permanently connected to earth.
CAUTION: Power cords and cables must not block access to device components or
drape where people could trip on them.
NOTE: Three-phase power cords provided with the router are approximately 14.75 ft (4.5 m)
in length. Single–phase power cords provided with the router are approximately 8.2 ft (2.5 m)
in length.
Table 58 on page 177 and Table 59 on page 178 provide specifications for the AC power cords for each
region supported. Figure 65 on page 178 and Figure 66 on page 178 illustrate the plug on the three-phase
Delta and Wye AC power cords.
Table 58: Three-Phase Delta and Wye AC Power Cord Specifications
Model NumberRegion
CBL-MX2000-3PH-DELTANorth America
CBL-MX2000-3PH-WYEEurope
177

Table of Contents

Other manuals for Juniper MX2020

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Juniper MX2020 and is the answer not in the manual?

Juniper MX2020 Specifications

General IconGeneral
BrandJuniper
ModelMX2020
CategoryNetwork Router
LanguageEnglish

Related product manuals