Temperature
Settings
Master
Controls
Temperature Limits
Setup
4-26
Part 1123087_02
3/2014 Nordson Corporation
Modifying Temperature Limits
Follow this procedure to change the number of degrees a heated zone can
increase or decrease from its setpoint temperature before a temperature alert
occurs. If the overtemperature or undertemperature condition is not resolved
within two minutes, the alert changes to a fault and the heaters automatically
switch off.
1.. From the Home screen, touch Master Controls > Settings >
Temperature.
2.. Touch Temperature Limits and use the keypad to enter the desired
values for Overtemperature and Undertemperature. Refer to Table4‐8
for the default and optional settings.
3.. Touch Done.
Done
Cancel
C
7 89
45 6
12 3
0
Temperature Limits
15
Over Temperature
Under Temperature
C
25
Home
Figure 4‐13 Temperature screen
Table 4‐8 Temperature Limits Default and Optional Settings
Button Description Default Setting Optional Settings
Temperature Limits Specifies the number of
degrees a heated zone can
increase or decrease from its
setpoint temperature before a
temperature alert occurs
Overtemperature:
15 °C (25 °F)
Undertemperature:
25 °C (50 °F)
50-60 °C
(10-110 °F)