D-132 Parameter Reference
AC30V series Variable Speed Drive
PNO
Name
Path(s)
Type
Default
Range
Units
WQ
View
Notes
MBus
0226
ENet Producing Inst
Setup::Communications::Option
Parameters::Option Comms::EtherNet IP
WORD 0064 CONFIG TECHNICIAN
00979
0227
ENet Consuming Inst
Same as PNO 226
WORD
0096
CONFIG
TECHNICIAN
00981
0228
Modbus RTU State
Monitor::Communications::Option
Parameters::Option Comms::Modbus RTU
USINT
(enum)
Same as PNO 46 NEVER OPERATOR
00983
0229
Modbus Device Address
Setup::Communications::Option
Parameters::Option Comms::Modbus RTU
USINT 1 1 to 247 CONFIG TECHNICIAN 7
00985
0230
Modbus RTU Baud Rate Same as PNO 229
USINT
(enum)
4
0:1200 BPS
1:2400 BPS
2:4800 BPS
3:9600 BPS
4:19200 BPS
5:38400 BPS
6:57600 BPS
7:76800 BPS
8:115200 BPS
CONFIG TECHNICIAN
00987
0231
Parity And Stop Bits Same as PNO 229
USINT
(enum)
0
0:EVEN, 1 STOP
1:ODD, 1 STOP
2:NONE, 2 STOP
3:NONE, 1 STOP
CONFIG TECHNICIAN
00989
0232
High Word First RTU
Same as PNO 229
BOOL
FALSE
CONFIG
TECHNICIAN
00991
0233
Modbus RTU Timeout
Same as PNO 229
TIME
3.000
0.000 to 65.000
s
CONFIG
TECHNICIAN
00993
0234
Modbus TCP State
Monitor::Communications::Option
Parameters::Option Comms::Modbus TCP
USINT
(enum)
Same as PNO 46 NEVER OPERATOR
00995
0235
High Word First TCP
Setup::Communications::Option
Parameters::Option Comms::Modbus TCP
BOOL FALSE CONFIG TECHNICIAN
00997
0236
Modbus TCP Timeout
Same as PNO 235
TIME
3.000
0.000 to 65.000
s
CONFIG
TECHNICIAN
00999
0237
Profibus State
Monitor::Communications::Option
Parameters::Option Comms::Profibus
USINT
(enum)
Same as PNO 46 NEVER OPERATOR
01001
0238
Profibus Node Address
Setup::Communications::Option
Parameters::Option Comms::Profibus
USINT 0 0 to 126 CONFIG TECHNICIAN 7
01003
0239
PROFINET State
Monitor::Communications::Option
Parameters::Option Comms::PROFINET IO
USINT
(enum)
0:SETUP
1:NW INIT
2:WAITING TO CONNECT
3:STOP MODE
4:CONNECTED
5:ERROR
6:RESERVED
7:EXCEPTION
8:NONE
NEVER OPERATOR
01005
0240
PROFINET Device Name
Same as PNO 239
STRING[32]
NEVER
OPERATOR
01007
0249
Braking Enable
Parameters::Motor Control::Braking
BOOL
TRUE
ALWAYS
TECHNICIAN
6
01025
0251
Brake Resistance Parameters::Motor Control::Braking REAL 100.00 0.01 to 1000.00
Ohm
s
ALWAYS TECHNICIAN 6
01029
0252
Brake Rated Power
Parameters::Motor Control::Braking
REAL
0.10
0.10 to 510.00
kW
ALWAYS
TECHNICIAN
6
01031
0253
Brake Overrating
Parameters::Motor Control::Braking
REAL
25.00
1.00 to 40.00
ALWAYS
ENGINEER
6
01033
0254
Braking Active
Parameters::Motor Control::Braking
BOOL
NEVER
TECHNICIAN
01035
0255
Autotune Enable
Setup::Motor Control::Autotune
Parameters::Motor Control::Autotune
BOOL FALSE STOPPED TECHNICIAN 2
01037
0256
Autotune Mode Same as PNO 255
USINT
(enum)
1
0:STATIONARY
1:ROTATING
STOPPED TECHNICIAN 6
01039
0257
Autotune Test Disable Same as PNO 255
WORD
(bitfield)
0000
0:Stator Resistance
1:Leakage Inductance
2:Magnetising Current
3:Rotor Time Constant
4:Encoder Direction
STOPPED TECHNICIAN 6
01041
www.comoso.com