D-132 Parameter Reference 
AC30V series Variable Speed Drive 
0226 
ENet Producing Inst 
Setup::Communications::Option 
Parameters::Option Comms::EtherNet IP 
WORD  0064      CONFIG  TECHNICIAN   
00979 
0228 
Modbus RTU State 
Monitor::Communications::Option 
Parameters::Option Comms::Modbus RTU 
  Same as PNO 46    NEVER  OPERATOR   
00983 
0229 
Modbus Device Address 
Setup::Communications::Option 
Parameters::Option Comms::Modbus RTU 
USINT  1  1 to 247    CONFIG  TECHNICIAN  7 
00985 
0230 
Modbus RTU Baud Rate  Same as PNO 229 
USINT 
(enum) 
4 
1:2400 BPS 
2:4800 BPS 
3:9600 BPS 
4:19200 BPS 
5:38400 BPS 
6:57600 BPS 
7:76800 BPS 
  CONFIG  TECHNICIAN   
00987 
0231 
Parity And Stop Bits  Same as PNO 229 
USINT 
(enum) 
0 
1:ODD, 1 STOP 
2:NONE, 2 STOP 
  CONFIG  TECHNICIAN   
00989 
0234 
Modbus TCP State 
Monitor::Communications::Option 
Parameters::Option Comms::Modbus TCP 
  Same as PNO 46    NEVER  OPERATOR   
00995 
0235 
High Word First TCP 
Setup::Communications::Option 
Parameters::Option Comms::Modbus TCP 
BOOL  FALSE      CONFIG  TECHNICIAN   
00997 
0237 
Profibus State 
Monitor::Communications::Option 
Parameters::Option Comms::Profibus 
  Same as PNO 46    NEVER  OPERATOR   
01001 
0238 
Profibus Node Address 
Setup::Communications::Option 
Parameters::Option Comms::Profibus 
USINT  0  0 to 126    CONFIG  TECHNICIAN  7 
01003 
0239 
PROFINET State 
Monitor::Communications::Option 
Parameters::Option Comms::PROFINET IO 
USINT 
(enum) 
 
1:NW INIT 
2:WAITING TO CONNECT 
3:STOP MODE 
4:CONNECTED 
5:ERROR 
6:RESERVED 
7:EXCEPTION 
  NEVER  OPERATOR   
01005 
Parameters::Motor Control::Braking 
0251 
Brake Resistance  Parameters::Motor Control::Braking  REAL  100.00  0.01 to 1000.00 
Ohm
ALWAYS  TECHNICIAN  6 
01029 
Parameters::Motor Control::Braking 
Parameters::Motor Control::Braking 
Parameters::Motor Control::Braking 
0255 
Autotune Enable 
Setup::Motor Control::Autotune 
Parameters::Motor Control::Autotune 
BOOL  FALSE      STOPPED  TECHNICIAN  2 
01037 
0256 
Autotune Mode  Same as PNO 255 
1 
  STOPPED  TECHNICIAN  6 
01039 
0257 
Autotune Test Disable  Same as PNO 255 
WORD 
(bitfield) 
0000 
1:Leakage Inductance 
2:Magnetising Current 
3:Rotor Time Constant 
  STOPPED  TECHNICIAN  6 
01041