Figure 6-146 Selecting Parallel Control
Make the necessary communication settings.
[sc_para_com_prot, 1, en_US]
Figure 6-147 Ethernet-interface settings
i
i
NOTE
Note that you must assign a separate IP address for each device.
i
i
NOTE
Note the hardware equipment of the device and the settings for the IEC 61850 communication (IEC 61850
Edition 2 required).
Under Device Information in DIGSI, change IEC 61850 Edition 1 to Edition 2.
Control Functions
6.9 Voltage Controller
478 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017