3-5
Chapter 3 Installing 4100ES MINIPLEX Components
Introduction to MINIPLEX Transponders (continued)
Local Mode
Specifications
Local Mode is supported by the following:
4100-3101/3104/3105 IDNet Card
4100-3106 IDNet Quick Connect Card
4100-3109 IDNet 2 Card
4100-3110 IDNet 2+2 Card
4100-5101/5102/5103 Expansion Power Supply NACs (including TrueAlert
Non-Addressable SmartSync appliances)
4100-5111/5112/5113 System Power Supply NACs (including TrueAlert
Non-Addressable SmartSync appliances)
4100-5125/5126/5127 Remote Power Supply NACs (including TrueAlert
Non-Addressable SmartSync appliances)
4100-5120/5121/5122 TrueAlert Power Supply NACs
4100-1214 to -1225, 4100-1228 to -1239, 4100-1314 to -1325, 4100-1328 to -1339 100W
Amplifier NACs
4100-1212/1213/1226/1227/1312/1313/1326/1327 Flex 50 Amplifier NACs
4009-9401 TrueAlert Addressable Controller
4100-1270 Phone Controller and 4100-1272/1273 Phone NAC cards
4009-9201/9301 IDNet NAC Extender
4100-5116 Expansion Signal Card
4100-6077 MX Digital Loop Card
Local Mode is NOT supported by, but can co-exist with, the following:
4100 Legacy cards
4100-3101 to 3103 Auxiliary Relay cards
4100-6048 VESDA Interface Kit
4100-6043/6044 RS-232/2120 Interfaces
4100-1280 to 1287 LED/Switch Annunciators
4100-1290 24-Point Graphic I/O Module
4602-9101 SCU/ 4602-9102 RCU
4603-9101 LCD Annunciator
4100-1210/1211/1311 Audio Controller Board
4100-6014 Network Interface Card
4100-6052 DACT
4100-3115 XA Loop Interface Card
4100-6065 BMUX COMMs Module
4100-6066 TFX Loop Interface
Bear in mind the following limitations when local mode is in effect:
If an alarm is already activated when local mode is initiated, the alarm remains activated in
local mode.
Software zones are not supported. Basic TrueAlert channels are supported.
Alarm verification is not supported. All alarms are reported immediately.
SMPL is not supported.
TrueAlarm sensors have fixed thresholds.

Table of Contents

Other manuals for Simplex 4100ES

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4100ES and is the answer not in the manual?

Simplex 4100ES Specifications

General IconGeneral
TypeFire Alarm Control Panel
DisplayLCD
Battery BackupYes
Model4100ES
ManufacturerSimplex
Communication ProtocolOptional Ethernet
Signaling Line Circuits (SLCs)Up to 10
Notification Appliance Circuits (NACs)Up to 10
Agency ListingsUL, FM, CSFM, MEA
Max Relay Circuits20
Communication PortsEthernet
Operating Temperature32°F to 120°F (0°C to 49°C)
HumidityUp to 93% RH, non-condensing