4.2 European Standards
252 YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
3. Ground the wire shielding on the drive side and motor side.
A - Drive
B - 10 m (32.8 ft.) maximum
C - Motor
D - Metal conduit
E - Grounding wire
Figure 4.15 Wiring the Drive and Motor
Note:
Use a braided shield cable for the drive and motor wiring or put the wires through a metal conduit.
The maximum wiring length between the drive and motor is 10 m (32.8 ft.). Keep the cable between the drive and motor as
short as possible.
Keep the grounding wire as short as possible.
4. Use a cable clamp to ground the motor cable to the metal plate.
Note:
Make sure that the protective ground wire complies with technical specifications and local safety standards.
A - Braided shield cable
B - Metal plate
C - Cable clamp (conductive)
Figure 4.16 Ground the Shield