Standards Compliance
4
4.2 European Standards
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual 253
A - Grounding surface (Remove any
paint or sealant.)
B - Enclosure panel
C - Metal plate
D - Drive
E - Ground the shield.
F - Motor
G - Motor cable (Braided shield
cable: max. 10 m (32.8 ft.))
H - Cable clamp
I - Grounding wire
J - EMC noise filter
Figure 4.17 EMC Noise Filter and Drive Installation Procedure
5. Connect the DC reactor to decrease harmonic distortion. Refer to DC Reactor on page 255 to select a DC
reactor.
Note:
To maintain compliance with IEC/EN 61000-3-2 on drive models 2004, 2006, 4002, and 4004, install a DC reactor.
The main circuit terminal block for the drive, and the terminal blocks for the DC reactor come in different shapes. The drive
has a European style terminal block, and the DC reactor has a round terminal block. Correctly prepare the ends of the
wiring.
Ground Wiring
WARNING! Electrical Shock Hazard. Do not remove covers or touch circuit boards while the drive is energized. Failure to obey
can cause death or serious injury.