EasyManua.ls Logo

YASKAWA GA700 - Page 651

YASKAWA GA700
1053 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter List
10
10.22 Parameters Changed by PM Motor Code Selection
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual 651
*1 Default settings vary depending on the setting of o2-04 (Drive Model Selection).
Table 10.9 SSR1 Series Motor Code Setting for Specification of 400 V at 1750 min
-1
(r/min)
No. Name Unit Motor Code (setting value of E5-01)
E5-01
PM Motor Code
Selection
- 123E 123F 1240 1242 1243 1244 1245 1246
Voltage Class V 400 400 400 400 400 400 400 400
Capacity kW 15 18 22 30 37 45 55 75
Motor Rotation
Speed
min
-1
1750 1750 1750 1750 1750 1750 1750 1750
E5-02
PM Motor Rated
Power (kW)
kW 15 18.50 22.00 30.00 37.00 45.00 55.00 75.00
E5-03
PM Motor Rated
Current (FLA)
A 27.5 33.4 39.8 52.0 65.8 77.5 92.7 126.6
E5-04
PM Motor Pole
Count
- 6 6 6 6 6 6 6 6
E5-05
PM Motor
Resistance (ohms/
phase)
Ω 0.272 0.207 0.148 0.235 0.079 0.054 0.049 0.029
E5-06
PM d-axis
Inductance (mH/
phase)
mH 10.30 8.72 6.81 5.4 4.08 3.36 3.16 2.12
E5-07
PM q-axis
Inductance (mH/
phase)
mH 12.77 11.22 8.47 7.26 5.12 3.94 3.88 2.61
E5-09
PM Back-EMF
Vpeak (mV/(rad/
s))
mVs/rad 498.8 509.5 503.9 561.7 528.5 558.1 623.8 594.5
E5-24
PM Motor
Induced Voltage
Constant 2 (Ke)
mV/(r/
min)
0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
E1-04
Maximum Output
Frequency
Hz 87.5 87.5 87.5 87.5 87.5 87.5 87.5 87.5
E1-05
Maximum Output
Voltage
V 380.0 380.0 380.0 380.0 380.0 380.0 380.0 380.0
E1-06 Base Frequency Hz 87.5 87.5 87.5 87.5 87.5 87.5 87.5 87.5
E1-09
Minimum Output
Frequency
Hz 4.4 4.4 4.4 4.4 4.4 4.4 4.4 4.4
C5-17 Motor Inertia kgm
2
0.046 0.055 0.064 0.116 0.140 0.259 0.31 0.42
L3-24
*1
Motor Accel Time
for Inertia Cal
s 0.102 0.101 0.098 0.130 0.127 0.193 0.191 0.187
n5-02
Motor
Acceleration Time
s 0.102 0.101 0.098 0.130 0.127 0.193 0.191 0.187
n8-49
d-Axis Cur
forHighEfficiency
Cont
% -15.5 -17.9 -15.1 -16.8 -14.1 -8.8 -9.6 -10.3
*1 Default settings vary depending on the setting of o2-04 (Drive Model Selection).
Table 10.10 SSR1 Series Motor Code Setting for Specification of 400 V at 1750 min
-1
(r/min)
No. Name Unit Motor Code (setting value of E5-01)
E5-01
PM Motor Code Selection - 1247 1248 1249 124A
Voltage Class V 400 400 400 400
Capacity kW 90 110 132 160
Motor Rotation Speed min
-1
1750 1750 1750 1750
E5-02 PM Motor Rated Power (kW) kW 90.00 110.00 132.00 160.00
E5-03
PM Motor Rated Current
(FLA)
A 160.4 183.3 222.9 267.7