Parameter Details
11
11.8 H: Terminal Functions
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual 901
■ 10: Alarm
Setting Function Description
10 Alarm
The terminal turns on when the drive detects a minor fault.
■ 11: Fault Reset Command Active
Setting Function Description
11 Fault Reset
Command Active
The terminal turns on when the drive receives the Reset command from the control circuit terminal,
serial communications, or the communication option.
■ 12: Timer Output
Setting Function Description
12 Timer Output
Use this setting when the drive uses the timer function as an output terminal.
Note:
Refer to “b4: Timer Function” for more information.
■ 13: Speed Agree 2
Setting Function Description
13 Speed Agree 2
The terminal activates when the output frequency is in the range of the frequency reference ± L4-04
[Speed Agree Detection Width (+/-)].
Note:
• The motor rotation direction does not have an effect on the detection function. The drive uses the L4-01 value as the forward/reverse
detection level.
• CLV and CLV/PM control use motor speed as the reference.
ON : The output frequency is in the range of “frequency reference ± L4-04”.
OFF : The output frequency is not in the range of “frequency reference ± L4-04”.
Figure 11.97 Speed Agree 2 Time Chart
■ 14: User-Set Speed Agree 2
Setting Function Description
14 User-Set Speed
Agree 2
The terminal activates when the output frequency is in the range of L4-03 [Speed Agree Detect
Level (+/-)] ± L4-04 [Speed Agree Detect Width (+/-)] and in the range of the frequency reference
± L4-04.
Note:
• The detection level configured with L4-03 is a signed value. The drive will only detect in one direction.
• CLV and CLV/PM control use motor speed as the reference.
ON : The output frequency is in the range of “L4-03 ± L4-04” and the range of frequency
reference ± L4-04.
OFF : The output frequency is not in the range of “L4-03 ± L4-04” or the in the range of frequency
reference ± L4-04.