DSP Components 375
© 2020, ATEÏS. All rights reserved.
Each of the Fire Alarm Message can be added in more than one Message Group and the name of
[Message Group] can be changed for users' preference. During the message paging, the playlist of
[Message Group] shall be played orderly from top to bottom [Warning > Fire Alarm > MG3].
Priority: Set the priority for Fire Alarm Message. Select the priority order for message output
when more than 1 message needs to be played in the same paging zone simultaneously.
Play Times: Set the play times of Fire Alarm Message (max.100 times or select [Repeat]
button for continuous play).
The play times is based on when all the [Message Group] has finished playing from top to
bottom.
Message Start Impulse Pin: Set the number of Logic Output signal pin when the message
starts paging.
Message Stop Impulse Pin: Set the number of Logic Output signal pin when the message
ends paging.
Message ACK Signal Pin: Set the number of ACK Signal Pin when Fire Alarm component
starts paging with high signal, and will be as low signal when the message ends.
Message Idle Signal Pin: Set the number of Message Idle Signal Pin when each [Message
Group] are in Idle Mode with high signal, and shall be as low signal without Idle Mode.
The following description of functionality included Prev/Normal/Post...etc. and parameters of each
[Message Group] shall be listed below.
Play Times: Set the time of [Message Group] (max.100 times).
The play times of [Message Group] is based on with the order of Prev>Norma>Post.
Idle Time: Set the Idle Time between the former and latter [Message Groups] (max.100
seconds).
Interrupt: Allow the interruption during the playback. If not, the message in Message Group will
be ended after the Fire Alarm stops.
Renew: Allow to recalculate the play times in [Message Group]. During the playback of
[Message Group], this setting shall be referred to whether to be recalculated or continued the
current play times once the status of EVAC Input has changed.
Behavior: Set the playback mode of message when the status of EVAC Input has changed.
There are three types of modes including [Continue Play], [Restart Play] and [Net Time
Continue Play].
o Continue Play: Continually play the message when changing to another paging zone.
o Restart Play: Start playing over again from Prev when changing to another paging zone.
o Next Time Continue Play: Start playing after the playing list of [Message Group] ends.
Active: Select to active the message playback of Prev/Post.