AH500 Hardware and Operation Manual
12-66
Error
code
Description
CPU
Status
LED indicator status
ERROR
BUS
FAULT
16#2010
1. The instruction does not support the device.
2. Encoding error
3. The instruction is a 16-bit instruction, but the
constant operand is a 32-bit code. (SM5)
Stop Blinking Keep
16#2011
The number of operands is incorrect. (SM5)
Stop
Blinking
Keep
16#2012
Incorrect division operation (SM0/SM5).
Self-defined
Blinking
Keep
16#2013
The value exceeds the range of values which can be
represented by the floating-point numbers. (SM0/SM5)
Self-defined Blinking Keep
16#2014
The task designated by TKON/YKOFF is incorrect, or
exceeds the range. (SM5)
Stop Blinking Keep
16#2015
There are more than 32 levels of nested program
structures supported by CALL. (SM0)
Self-defined Blinking Keep
16#2016
There are more than 32 levels of nested program
structures supported by FOR/NEXT. (SM0/SM5)
Self-defined Blinking Keep
16#2017
The number of times FOR is used is different from the
number of times NEXT is used. (SM5)
Stop Blinking Keep
16#2018
There is a label after FEND, but there is no SRET.
There is SRET, but there is no label. (SM5)
Stop Blinking Keep
16#2019
The interrupt task is not after FEND. (SM5)
Stop
Blinking
Keep
16#201A
IRET/SRET is not after FEND. (SM5)
Stop
Blinking
Keep
16#201B
There is an interrupt task, but there is no IRET.
There is IRET, but there is not interrupt task. (SM5)
Stop Blinking Keep
16#201C
End is not at the end of the program. (SM5)
Stop
Blinking
Keep
16#201D
There is CALL, but there is no MAR. (SM5)
Stop
Blinking
Keep
16#201E
The function code used in MODRW is incorrect.
(SM102/SM103)
Self-defined Blinking Keep
16#201F
The length of the data set in MODRW is incorrect.
(SM102/SM103)
Self-defined Blinking Keep
16#2020
The communication command received by using
MODRW is incorrect. (SM102/SM103)
Self-defined Blinking Keep
16#2021
The checksum of the command received is incorrect.
(SM102/SM103)
Self-defined Blinking Keep
16#2022
The format of the command used in MODRW does not
conform to the ASCII format. (SM102/SM103)
Self-defined Blinking Keep
16#2023
A communication timeout occurred in the execution of
MODRW instruction. (SM120/SM103)
Self-defined Blinking Keep
16#2024
The setting value of the communication timeout is
invalid in the execution of RS instruction.
(SM120/SM103)
Self-defined Blinking Keep
16#2025
A communication timeout occurred in the execution of
RS instruction. (SM120/SM103)
Self-defined Blinking Keep
16#2026
The interrupt index is abnormal in the execution of RS
instruction. (SM102/104)
Self-defined OFF Keep
16#2027
The execution of FWD instruction is abnormal.
(SM102/103)
Self-defined Blinking Keep
16#2028
The execution of REV instruction is abnormal.
(SM102/103)
Self-defined Blinking Keep
16#2029
The execution of STOP instruction is abnormal.
(SM102/103)
Self-defined Blinking Keep
16#202A
The execution of RSDT instruction is abnormal.
(SM102/103)
Self-defined Blinking Keep