Chapter 12 Troubleshooting
12-67
Error
code
Description
CPU
Status
LED indicator status
ERROR
BUS
FAULT
16#202B
The execution of RSTEF instruction is abnormal.
(SM102/103)
Self-defined Blinking Keep
16#202C
|
16#204B
I/O interrupt service routine 0 does not exist.
|
I/O interrupt service routine 31 does not exist.
Stop Blinking Keep
16#2054
|
16#2127
External interrupt service routine 40 does not exist.
|
External interrupt service routine 251 does not exist.
Stop Blinking Keep
16#2128
An action in a sequential function chart (SFC) is
incorrectly assigned qualifiers related to time.
(SM0/SM1)
Self-defined Blinking Keep
16#2129
The modifier R is assigned to an action in a sequential
function chart (SFC) incorrectly. (SM0/SM1)
Self-defined Blinking Keep
16#212A
MC/MCR instruction cannot be used in interrupt or
subroutine. (SM5)
Self-defined Blinking Keep
16#6000
Ethernet connection error (SM1106)
Continue
Blinking
Keep
16#6001
Illegal IP address (SM1107)
Continue
Blinking
Keep
16#6002
Illegal netmask address (SM1107)
Continue
Blinking
Keep
16#6003
Illegal gateway mask (SM1107)
Continue
Blinking
Keep
16#6004
The IP address filter is set incorrectly. (SM1108)
Continue
Blinking
Keep
16#6006
The static ARP table is set incorrectly. (SM1108)
Continue
Blinking
Keep
16#6007
The NTP client service is set incorrectly. (SM1380)
Continue
Blinking
Keep
16#6008
Illegal network number (SM1107)
Continue
Blinking
Keep
16#6009
Illegal node number (SM1107)
Continue
Blinking
Keep
16#600A
TCP connection failure (SM1090)
Continue
Keep
Keep
16#600B
UDP connection failure (SM1091)
Continue
Keep
Keep
16#600C
The TCP socket has been used. (SM1109)
Continue
Keep
Keep
16#600D
The RJ45 port is not connected.
Continue
Keep
Keep
16#600E
An RJ45 port on AH10EN-5A is not connected to a
network cable.
Continue Keep Keep
16#600F
The maximum MODBUS TCP connection is reached.
(SM1089)
Continue Blinking Keep
16#6010
BOOTP IP is set incorrectly. (SM1107)
Continue
Keep
Keep
16#6011
BOOTP Gateway is set incorrectly. (SM1107)
Continue
Keep
Keep
16#6012
Duplicated IP address (SM1107)
Continue
Blinking
Keep
16#6013
DNS address is set incorrectly. (SM1107)
Continue
Keep
Keep
16#6100
The email connection is busy. (SM1113)
Continue
Keep
Keep
16#6101
The trigger in the email is set incorrectly. (SM1112)
Continue
Blinking
Keep
16#6102
The interval of sending the email is set incorrectly.
(SM1112)
Continue Blinking Keep
16#6103
The device containing the data specified as the
attachment exceeds the device range. (SM1112)
Continue Blinking Keep
16#6104
The attachment in the email does not exist. (SM1113)
Continue
Keep
Keep
16#6105
The attachment in the email is oversized. (SM1113)
Continue
Keep
Keep
16#6106
The SMTP server address is incorrect. (SM1112)
Continue
Blinking
Keep
16#6107
There is an SMTP server response timeout. (SM1113)
Continue
Keep
Keep
16#6108
SMTP authentication error (SM1112)
Continue
Blinking
Keep
16#6110
The SMTP server needs to be authenticated. (SM1112)
Continue
Blinking
Keep
16#6111
The specified email address does not exist. (SM1112)
Continue
Blinking
Keep
16#6200
The remote IP address set in the TCP socket function
is illegal. (SM1196)
Continue Blinking Keep