AH500 Hardware and Operation Manual
12-70
Error
code
Description
CPU
Status
LED indicator status
ERROR
BUS
FAULT
16#7412
Owing to the fact that SW1 is ON, data can not be
downloaded to the CPU module.
Continue Keep Keep
16#757D
The remaining number of PLC password guesses is 0.
Continue
Keep
Keep
16#757E
The PLC password entered is incorrect.
Continue
Keep
Keep
16#8105
The program downloaded to the CPU module is
incorrect. The syntax downloaded is incorrect.
Continue Keep Keep
16#8106
The program downloaded is incorrect. The length of
the machine code exceeds the limit.
Continue Keep Keep
16#8107
The program downloaded is incorrect. The length of
the source code exceeds the limit.
Continue Keep Keep
16#8230
A CPU parameter downloaded is incorrect. The IP
address is illegal.
Continue Keep Keep
16#8231
A CPU parameter downloaded is incorrect. The
netmask address is illegal.
Continue Keep Keep
16#8232
A CPU parameter downloaded is incorrect. The
gateway address is illegal.
Continue Keep Keep
16#8233
A CPU parameter downloaded is incorrect. The IP
address filter is set incorrectly.
Continue Keep Keep
16#8235
A CPU parameter downloaded is incorrect. The static
ARP table is set incorrectly.
Continue Keep Keep
16#8236
A CPU parameter downloaded is incorrect. The NTP
client service is set incorrectly.
Continue Keep Keep
16#8239
A CPU parameter downloaded is incorrect. The email
sending function is set incorrectly.
Continue Keep Keep
16#823A
A CPU parameter downloaded is incorrect. The
condition for the sending of an email is set incorrectly.
Continue Keep Keep
16#823B
A CPU parameter downloaded is incorrect. A TCP
socket is set incorrectly.
Continue Keep Keep
16#823C
A CPU parameter downloaded is incorrect. A UDP
socket is set incorrectly.
Continue Keep Keep
16#823E
A CPU parameter downloaded is incorrect. The eeb
function is set incorrectly.
Continue Keep Keep
16#8240
A CPU parameter downloaded is incorrect. The data
exchange by means of Ethernet is set incorrectly
Continue Keep Keep
16#8241
The setting of a DNS server is incorrect.
Continue
Keep
Keep
16#8522
A module configuration is being scanned.
Continue
Keep
Keep
16#853B
An I/O module is not configured.
Continue
Keep
Keep
16#853C
An I/O module does not exist.
Continue
Keep
Keep
16#854B
An I/O module is not configured.
Continue
Keep
Keep
16#854C
An I/O module does not exist.
Continue
Keep
Keep
16#8572
The checksum of the module configuration table is
incorrect.
Continue Keep Keep
16#8576
The checksum of the module parameter setting is
incorrect.
Continue Keep Keep
16#857A
The checksum of the module parameter mapping table
is incorrect.
Continue Keep Keep
16#85E1
An I/O interrupt number is incorrect.
Continue
Keep
Keep
16#85E2
An I/O interrupt service routine does not exist.
Continue
Keep
Keep
16#860F
System restoration error
Continue
Blinking
Blinking
16#8611
No memory card exists, or the memory card format is
incorrect.
Continue Keep Keep