AH500 Hardware and Operation Manual
2-30
Model
Item
AH16AN01R
-5A
AH16AP11R
-5A
AH16AN01T
-5A
AH16AP11T
-
5A
AH16AN01P
-5A
AH16AP11P
-5A
AH16AN01S
-5A
Bulb
20 W (24 VDC)
100 W (230 VAC)
2 W (24 VDC) 2 W (24 VDC) 60 W AC
Maximum
output
frequency
*1
Resistance
1 Hz 100 Hz 100 Hz 10 Hz
Inductance
0.5 Hz 0.5 Hz 0.5 Hz -
Bulb 1 Hz 10 Hz 10 Hz 10 Hz
Maximum
Response
time
OFFON
10 ms 0.5 ms 0.5 ms
1 ms+0.5
AC cycles
ONOFF
Weight
225g 225g 190g 190g 190g 190g 190g
Model
Item
AH32AN02T
-5A
AH32AN02P
-5A
AH32AN02
T-5B
AH32AN02
P-5B
AH32AN02
T-5C
32AN02P-
5C
AH64AN02T
-5C
AH64AN02P
-5C
Number of outputs
32
32
32
32
32
32
64
64
Connector type
Removable
terminal block
DB37 connector Latch connector
Output type
TransistorT (sinking)
Transistor-P (sourcing)
Voltage specifications
12~30 VDC
*2
Electrical
isolation/Voltage
Opto-coupler; 500VAC
Maximum
load
Resistance
0.1 A/output (1 A/COM)
Inductance
Not applicable
Bulb
Not applicable
Maximum
output
frequency
*1
Resistance
100 Hz
Inductance
-
Bulb
-
Maximum
Response
time
OFFON
0.5 ms
ONOFF
Weight
180g 180g 150g 150g 140g 140g 220g 220g
*1: The scan cycle affects the frequency.
*2: The terminals UP and ZP needs to be connected to the 24 VDC auxiliary power supply (-15%~+20%), and
the rated current consumption is 1 mA/output.
*3: Life cycle curve: The lifetime of a relay terminal varies with the working voltage, the load type (the power
factor cosψ, the time constant t(L/R)), and the current passing through the terminal. The relation is shown
in the life cycle curve below.
Contact Current(A)
20
0.5
0.1
0.2
30
50
0.3 0.7
1 2
200
300
500
100
1000
2000
3000
Operation(X10 )
3
120VAC Resistive
30VDC Inductive(t=7ms)
240VAC Inductive(cos 0.4)
ψ
=
120VAC Inductive(cos =0.4)
ψ
30VDC
Inductive