The
Autostart:
function is activated (default setting).
In machines with the existing option for electronic thermal management (ETM), a duration of
60 s for autostart is defined by default.
If a value for parameter
Autostart:
has been additionally set, it is added to the 60 s.
Precondition Password access level 2 is activated
1. Open the 5.4
<Configuration – Compressor start>
menu.
2. Press the «Enter» key.
The
Compressor start
menu is displayed.
8 8 p s i 0 8 : 1 5 A M 1 7 6 ° F
Header
5.4 Compressor start
Menu
▶1 Compressor on
Active line
▶2 Compressor off
·········
Autostart: ☑
Autostart activated
Target 10s ¦ Actual 0s
Set/expiring delay time
·········
Setting the Autostart delay time
If you operate several machines, it is best to start them in sequence.
Use the "Delay time for Autostart" table to plan the time-delayed machine start. In the "Start
period" column, enter for each individual machine the actual time required for the first possi‐
ble LOAD operation. Add these values cumulatively in the “Delay time” column. Enter the val‐
ue of the delay time of each machine in the corresponding controller.
The first machine may start immediately and does not require a delay time.
Machine number Start time [sec] Delay time [sec]
1 –– ––
2
3
4
5
6
7
8
9
10
11
12
13
14
15
8 Initial Start-up
8.5 Configuring machine start and stop
100
User Manual Controller
SIGMA CONTROL 2 SCREW FLUID ≥5.1.2 No.: 9_9450 13 USE