Message Possible cause Remedy
1275 W
AIR%d.0%d - short-
circuit
Short circuit in line for indicated analog
input.
Check line path and sensor
connection.
1276 W
AIR%d.0%d - open
circuit
Wire break in line for indicated analog in‐
put.
Check line path and sensor
connection.
1277 W
AIR%d.0%d - sensor
fault
Sensor fault at indicated analog input. Check line path and sensor
connection.
1278 W
AIR%d.0%d - open
circuit
Wire break in line for indicated analog in‐
put.
Check line path and sensor
connection.
1280 W
AIR%d.0%d - accidental
ground
Ground fault in line for ext. sensor at ana‐
log input.
Check line path and sensor
connection.
1281 W
AIR%d.0%d - short-
circuit
Short circuit in line for indicated analog
input.
Check line path and sensor
connection.
1282 W
AIR%d.0%d - open
circuit
Wire break in line for indicated analog in‐
put.
Check line path and sensor
connection.
1283 W
AIR%d.0%d - sensor
fault
Sensor fault at indicated analog input. Check line path and sensor
connection.
1284 W
AIR%d.0%d - open
circuit
Wire break in line for indicated analog in‐
put.
Check line path and sensor
connection.
1286 W
AIR%d.0%d - accidental
ground
Ground fault in line for ext. sensor at ana‐
log input.
Check line path and sensor
connection.
1287 W
AIR%d.0%d - short-
circuit
Short circuit in line for indicated analog
input.
Check line path and sensor
connection.
1288 W
AIR%d.0%d - open
circuit
Wire break in line for indicated analog in‐
put.
Check line path and sensor
connection.
1289 W
AIR%d.0%d - sensor
fault
Sensor fault at indicated analog input. Check line path and sensor
connection.
1290 W
AIR%d.0%d - open
circuit
Wire break in line for indicated analog in‐
put.
Check line path and sensor
connection.
Tab. 88 Warning messages and remedies