EasyManua.ls Logo

KAESER SIGMA CONTROL 2 - External messages menu; Entering the message text

KAESER SIGMA CONTROL 2
246 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Establishing the electrical connection
Contact A open: SIGMA CONTROL 2 controls with system setpoint pressure pB
Contact A closed: SIGMA CONTROL 2 controls with system setpoint pressure pA
B 1.1: Pressure switch for system setpoint pressure pB
B 1.2: Pressure switch for system setpoint pressure pA
07-S0629
A
-K3
A1
A2
Fig. 38 Machine with pressure switch regulation
A Floating relay contact SIGMA CONTROL 2
Make the electrical connection according to the diagram.
Set the system setpoint pressure pA and pB.
Precondition Password access level 2 is activated.
The electrical connection is made.
1. Open the
<5.2.2 – Pressure control – Pressure settings>
menu (see chapter 8.4.1).
2. Use «Up» or «Down» to select the
pASP
line.
3. Press «Enter».
The setting mode is active.
The
Setpoint pressure pA
display flashes.
8 8 p s i 0 8 : 1 5 A M 1 7 6 ° F
Header
5.2.2 Pressure settings
Menu
Setpoint pressure
pA SP: 123psi ¦ SD: −7.3psi
Active line
pB SP: 119psi ¦ SD: −7.3psi
·········
System pressure low
< 72.5psi ¦ SD: 7.2psi
8 Initial Start-up
8.10 Configuring the machine for master control
146
User Manual Controller
SIGMA CONTROL 2 SCREW FLUID ≥5.1.2 No.: 9_9450 13 USE

Table of Contents

Other manuals for KAESER SIGMA CONTROL 2