Machine number Start time [sec] Delay time [sec]
16
Tab. 62 Autostart delay time
Precondition Password access level 2 is activated.
1. Open the 5.4
Compressor start
menu.
2. Using the «Up» or «Down» key, select the line
Target
.
8 8 p s i 0 8 : 1 5 A M 1 7 6 ° F
Header
5.4 Compressor start
Menu
â–¶1 Compressor on
â–¶2 Compressor off
·········
Autostart: ☑
Autostart activated
Target 10s ¦ Actual 0s
Active line, set/expiring delay time
·········
3. Press the «Enter» key.
The
Target
indicator flashes.
4. Use «Up» or «Down» key to set the time delay in seconds.
8 8 p s i 0 8 : 1 5 A M 1 7 6 ° F
Header
5.4 Compressor start
Menu
â–¶1 Compressor on
Active line
â–¶2 Compressor off
·········
Autostart: ☑
Autostart activated
Target 12s ¦ Actual 0s
Active line, set/expiring delay time
·········
5. Press the «Enter» key.
The setting is applied accordingly.
6. Press the «Escape» key repeatedly to exit the menu.
Result The delay time for an Autostart after a power failure has been adjusted from 10 s to 12 s.
8 Initial Start-up
8.5 Configuring machine start and stop
No.: 9_9450 13 USE
User Manual Controller
SIGMA CONTROL 2 SCREW FLUID ≥5.1.2
101

Table of Contents

Other manuals for KAESER SIGMA CONTROL 2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KAESER SIGMA CONTROL 2 and is the answer not in the manual?

KAESER SIGMA CONTROL 2 Specifications

General IconGeneral
Controller TypeMicroprocessor-based
ModelSIGMA CONTROL 2
ManufacturerKAESER
Input Voltage24 V DC
Protection ClassIP54
Communication ProtocolsModbus, Profibus
Data LoggingComprehensive data logging
Remote MonitoringYes
Communication InterfaceEthernet