The «Enter» key affects only the active line.
In some lines, you can change more than one parameter.
In this case, you must first select the specific parameter with the «Left» or «Right» keys.
Resetting current parameters
In order to reset current parameters to zero, activate the check box for
Reset
in the active line of
the display.
First, press «Enter» to switch into setting mode. The check box
Reset
will flash.
You then press «Up». The check box is activated and flashes.
Press «Enter» to save the settings.
The display no longer flashes and the parameters are reset. The check box for
Reset
is again de‐
activated.
Check box
Reset
Status
☒ Activated
☐ Deactivated
Tab. 29 Reset check box status
5.3.4 Activating keys with check boxes
Certain keys of the SIGMA CONTROL 2 are locked by default. Activate the corresponding check
boxes in the active line of the display to unlock these keys.
First, press «Enter» to switch into setting mode. The check box will flash.
You then press «Up». The check box is activated and flashes.
Press «Enter» again to save the settings.
The display line no longer flashes and the key is activated.
Proceed correspondingly to deactivate a key.
Check box Status
☑ Activated
☐ Deactivated
Tab. 30 Check box status
5.4 Access control
Access to the controller is gained via a user name and password combination.
By default, users log in using an RFID Equipment Card. Alternatively, a user name and password
can be entered manually.
On switching the controller on, the lowest level of access (level 0) is activated.
A further access level is available: Access level 2.
Access level 2 allows you to set and display further parameters.
In the absence of any key being pressed, the access level will return automatically to level 0 after
10 minutes.
5 Design and Function
5.4 Access control
No.: 9_9450 13 USE
User Manual Controller
SIGMA CONTROL 2 SCREW FLUID ≥5.1.2
25