KAESER SIGMA CONTROL 2 - Setting the master control with local;LOAD remote contact 3)

KAESER SIGMA CONTROL 2
246 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7. Press «Enter».
The setting is applied.
Activating the remote control
Activate remote control see chapter 8.2.13.
Result SIGMA CONTROL 2 remote control is activated.
The bus master can remotely control the SIGMA CONTROL 2.
8.10.4 Interconnection of two machines in master/slave operation
Example 1 Two machines with different flow rates
A timer program that can be configured on the master switches between the
pA
and
pB
set-point
pressures. The machine with the high flow rate is the master and the machine with the lower flow
rate is the slave.
Operating mode of load control on master:
Local mode pA/pB Clock
.
During periods of peak demand of compressed air, the master is regulated (in accordance
with the time program) to the set-point pressure
pA
and the signal for using the set-point
pressure
pB
is transmitted to the slave.
During periods of low air demand, the master is regulated (in accordance with the timer pro‐
gram) to set-point pressure
pB
(e.g. at weekends). The slave receives the information, to
use set-point pressure
pA
now.
Operating mode of load control on slave: Remote mode pA/pB SC2.
At peak air demand times, pressure is regulated to the
pB
set-point pressure and at times
with low air demand to set-point pressure
pA
.
At times with lower compressed air demand, the machine is correspondingly used more fre‐
quently.
Example 2: Two machines with equal flow rates
A timer that can be set on the master switches between the
pA
and
pB
set-point pressures. The
set-point pressures
pA
and
pB
are set the same for both machines.
Operating mode of load control on master:
Local mode pA/pB Cycle
.
The timer ensures even loading of both machines.
E.g. if the first start
pA
is selected as the start time, the master regulates for cycle time 1 at
set-point pressure
pA
and sends the slave the signal to use set-point pressure
pB
. During
cycle time 2, the master regulates to set-point pressure
pB
and signals to the slave to regu‐
late to set-point pressure
pA
. .
Operating mode of load control on slave:
Remote mode pA/pB SC2
.
Depending on the specification by the master, the slave regulates to set-point pressure
pA
or pB. See example for the master:
Cycle time 1 = set-point pressure
pB
Cycle pressure 2 = set-point pressure
pA
8 Initial Start-up
8.10 Configuring the machine for master control
No.: 9_9450 13 USE
User Manual Controller
SIGMA CONTROL 2 SCREW FLUID ≥5.1.2
131