7. Press «Enter».
The setting is applied.
Activating the remote control
Activate remote control see chapter 8.2.13.
Result SIGMA CONTROL 2 remote control is activated.
The bus master can remotely control the SIGMA CONTROL 2.
8.10.4 Interconnection of two machines in master/slave operation
Example 1 Two machines with different flow rates
A timer program that can be configured on the master switches between the
pA
and
pB
set-point
pressures. The machine with the high flow rate is the master and the machine with the lower flow
rate is the slave.
Operating mode of load control on master:
Local mode pA/pB Clock
.
During periods of peak demand of compressed air, the master is regulated (in accordance
with the time program) to the set-point pressure
pA
and the signal for using the set-point
pressure
pB
is transmitted to the slave.
During periods of low air demand, the master is regulated (in accordance with the timer pro‐
gram) to set-point pressure
pB
(e.g. at weekends). The slave receives the information, to
use set-point pressure
pA
now.
Operating mode of load control on slave: Remote mode pA/pB SC2.
At peak air demand times, pressure is regulated to the
pB
set-point pressure and at times
with low air demand to set-point pressure
pA
.
At times with lower compressed air demand, the machine is correspondingly used more fre‐
quently.
Example 2: Two machines with equal flow rates
A timer that can be set on the master switches between the
pA
and
pB
set-point pressures. The
set-point pressures
pA
and
pB
are set the same for both machines.
Operating mode of load control on master:
Local mode pA/pB Cycle
.
The timer ensures even loading of both machines.
E.g. if the first start
pA
is selected as the start time, the master regulates for cycle time 1 at
set-point pressure
pA
and sends the slave the signal to use set-point pressure
pB
. During
cycle time 2, the master regulates to set-point pressure
pB
and signals to the slave to regu‐
late to set-point pressure
pA
. .
Operating mode of load control on slave:
Remote mode pA/pB SC2
.
Depending on the specification by the master, the slave regulates to set-point pressure
pA
or pB. See example for the master:
Cycle time 1 = set-point pressure
pB
Cycle pressure 2 = set-point pressure
pA
8 Initial Start-up
8.10 Configuring the machine for master control
No.: 9_9450 13 USE
User Manual Controller
SIGMA CONTROL 2 SCREW FLUID ≥5.1.2
131

Table of Contents

Other manuals for KAESER SIGMA CONTROL 2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KAESER SIGMA CONTROL 2 and is the answer not in the manual?

KAESER SIGMA CONTROL 2 Specifications

General IconGeneral
Controller TypeMicroprocessor-based
ModelSIGMA CONTROL 2
ManufacturerKAESER
Input Voltage24 V DC
Protection ClassIP54
Communication ProtocolsModbus, Profibus
Data LoggingComprehensive data logging
Remote MonitoringYes
Communication InterfaceEthernet