1. Open the menu 3.1
<Operating data – Operating hours>
.
8 8 p s i 0 8 : 1 5 A M 1 7 6 ° F
Header
3.1 Operating hours
Menu
Compressor 3050h
Active line
On load 3030h
Motor 3050h
Compressor block 3050h
SIGMA CONTROL 2 3050h
2. Using the «Up» or «Down» key, select the line
Compressor block
.
3. Press «Enter».
The runtime display flashes.
8 8 p s i 0 8 : 1 5 A M 1 7 6 ° F
Header
3.1 Operating hours
Menu
Compressor 3050h
On load 3030h
Motor 3050h
Compressor block 0h
Active line
SIGMA CONTROL 2 3050h
4. Use «Down» or «Up» key to set the value for operating hours to zero.
5. Press «Enter».
The setting is applied accordingly.
6. Press «Escape» repeatedly to leave this menu.
Result The operating hours for the new airend are set to
0 h
.
9.8.2 Checking the switching cycles
The system monitors the usage times of safety-relevant components to ensure the proper
condition of all safety-relevant functions. Depending on the component, the usage time may
be defined by run time or switching cycles. For the main contactor, the usage time is defined
by the maximum permissible number of switching cycles.
The main contactor switching cycle counter in SIGMA CONTROL 2 records the number of
switching cycles and generates a warning message when the maximum permissible number
of switching cycles is exceeded.
When this warning message is generated, the safety-relevant function is no longer ensured.
The main contactor must be replaced!
➤ Follow all instructions carefully.
Displaying switching cycles
Precondition Password access level 2 is activated
1. Open the 3.2
<Operating data – Switching cycles>
menu.
9 Operation
9.8 Displaying operating data
No.: 9_9450 13 USE
User Manual Controller
SIGMA CONTROL 2 SCREW FLUID ≥5.1.2
183

Table of Contents

Other manuals for KAESER SIGMA CONTROL 2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KAESER SIGMA CONTROL 2 and is the answer not in the manual?

KAESER SIGMA CONTROL 2 Specifications

General IconGeneral
Controller TypeMicroprocessor-based
ModelSIGMA CONTROL 2
ManufacturerKAESER
Input Voltage24 V DC
Protection ClassIP54
Communication ProtocolsModbus, Profibus
Data LoggingComprehensive data logging
Remote MonitoringYes
Communication InterfaceEthernet