4. Use «Up» or «Down» to set the
pA
value.
5. Press «Enter».
The setting is applied.
6. If necessary, adjust the value for
SD
in the same manner.
7. If necessary, adjust the value for
pB/SD
in the same manner.
8. Press «Escape» repeatedly to leave this menu.
Set clock program
Set the clock program as described in chapter 8.9.2.
8.10.9 Examples of time settings for equal overall load
Requirement:
Two machines of the same capacity are to be equally loaded. Versions A, B and C describe the
different possibilities of achieving this requirement.
A detailed description for configuring a clock or timing program can be found in Chapter 8.9.
Variant A: Daily switch between system setpoint pressure pA and system setpoint pressure pB af‐
ter 24 hours
The compressors start with a system setpoint pressure
pB
at 0:00 hours. A timer triggers the
switch between system setpoint pressure
pA
and system setpoint pressure
pB
(local operating
mode:
pA/pB Cycle
local mode).
Precondition The setpoint pressure
pA
/
pB
is configured the same for both machines.
Establish a cycle with the following switching points:
Cycle time
pA
: 24 h
Cycle time
pB
: 24 h
Start
pB
: 00:00AM
Variant B: Equal duty cycle during the day
A timer triggers the switch between system setpoint pressure
pA
and system setpoint pressure
pB
(local operating mode
pA/pB Clock
.
Precondition The system setpoint pressure
pA
/
pB
is configured the same for both machines.
The clock program is set up using the following switching points:
No.: Weekday Time Network nominal pressure
01 Mon-Sun 00:00AM
pA
On
02 Mon-Sun 06:30AM
pB
On
03 Mon-Sun 12:00PM
pA
On
04 Mon-Sun 05:00PM
pB
On
Tab. 72 Example for a clock program for equal duty cycling during the day
8 Initial Start-up
8.10 Configuring the machine for master control
150
User Manual Controller
SIGMA CONTROL 2 SCREW FLUID ≥5.1.2 No.: 9_9450 13 USE

Table of Contents

Other manuals for KAESER SIGMA CONTROL 2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KAESER SIGMA CONTROL 2 and is the answer not in the manual?

KAESER SIGMA CONTROL 2 Specifications

General IconGeneral
Controller TypeMicroprocessor-based
ModelSIGMA CONTROL 2
ManufacturerKAESER
Input Voltage24 V DC
Protection ClassIP54
Communication ProtocolsModbus, Profibus
Data LoggingComprehensive data logging
Remote MonitoringYes
Communication InterfaceEthernet