8.10.7 Setting the setpoint pressure pre-selection via remote contact
The signal to changeover from setpoint pressure
pA
to setpoint pressure
pB
comes from an input
contact. If there is a signal at the input then system pressure is regulated on setpoint pressure
pB
.
Overview
â– Setting up remote contact mode pA/pB
â– Assigning the remote contact input
â– Activating the remote control
➤ Configuring the setpoint pressure pre-selection as described.
8.10.7.1 Setting up remote contact mode pA/pB
Precondition The electrical connection is made.
Password access level 2 is activated.
1. Select the 5.2.3
<Configuration – Pressure control – Load control>
menu.
2. Use «Up» or «Down» to select the
Remote mode
line.
3. Press «Enter».
The currently active operating mode flashes.
8 8 p s i 0 8 : 1 5 A M 1 7 6 ° F
Header
5.2.3 Load control
Menu
Local mode : pB
Remote mode : pA/pB RC
Active line
------------------------------
â–¶1 pA/pB Clock
·········
pA/pB Cycle
4. Use «Up» or «Down» to set the
pA/pB RC
input.
5. Press «Enter».
Result The
pA/pB RC
operating mode is set.
8.10.7.2 Assigning the remote contact input
A spare input can be found in the machine circuit diagram.
1. Use «Up» or «Down» to select the
pA/pB RC
line.
8 Initial Start-up
8.10 Configuring the machine for master control
144
User Manual Controller