EasyManua.ls Logo

KAESER SIGMA CONTROL 2 - Assigning and activating the output; Output measured values on the display

KAESER SIGMA CONTROL 2
246 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Period t1–t7: high air demand Period t8–t14: low air demand
t5:
SK also switches to LOAD.
System pressure pNloc begins to rise.
t12:
SK switches to LOAD.
System pressure pNloc begins to rise.
t6:
SK switches to IDLE.
t13:
SK switches to IDLE.
t7:
BSD switches to IDLE.
t14:
BSD switches to IDLE.
Tab. 71 Function diagram
Fig. 39 Function diagram
SD Switching differential
p Pressure
t Time
Set the system setpoint pressure pA and pB.
Precondition Password access level 2 is activated.
1. Open the
<5.2.2 – Pressure control – Pressure settings>
menu (see chapter 8.4.1).
2. Use «Up» or «Down» to select the
pASP
line.
8 8 p s i 0 8 : 1 5 A M 1 7 6 ° F
Header
5.2.2 Pressure settings
Menu
Setpoint pressure
pA SP: 123psi ¦ SD: −7.3psi
Active line
pB SP: 119psi ¦ SD: −7.3psi
·········
System pressure low
< 72.5psi ¦ SD: 7.2psi
3. Press «Enter».
The
pA
display flashes.
8 Initial Start-up
8.10 Configuring the machine for master control
No.: 9_9450 13 USE
User Manual Controller
SIGMA CONTROL 2 SCREW FLUID ≥5.1.2
149

Table of Contents

Other manuals for KAESER SIGMA CONTROL 2