1. Open the 5.3.2
<Configuration – Control mode – DUAL>
menu.
8 8 p s i 0 8 : 1 5 A M 1 7 6 ° F
Header
5.3.2 DUAL
Menu
Idle period
Target 240s ¦ Actual 0s
Active line
2. Using the «Up» or «Down» key, select the line
Target
.
8 8 p s i 0 8 : 1 5 A M 1 7 6 ° F
Header
5.3.2 DUAL
Menu
Idle period
Target 300s ¦ Actual 0s
Increased idle time (e.g. 300 s)
3. Press the «Enter» key.
The seconds display flashes.
4. Use the «Up» or «Down» key to set the seconds.
5. Press the «Enter» key.
The setting is applied accordingly.
6. Press the «Escape» key repeatedly to exit the menu.
8.6.3 Setting the QUADRO control mode
When the minimum running period has elapsed, the machine switches from IDLE to READY. The
expired duration of the unloaded period controls whether the machine switches from IDLE to
READY only after expiration of the set unloaded period or after expiration of the relief period.
Precondition Password access level 2 is activated.
The QUADRO control mode is set.
1. Open the 5.3.3
<Configuration – Control mode – QUADRO>
menu.
8 8 p s i 0 8 : 1 5 A M 1 7 6 ° F
Header
5.3.3 QUADRO
Menu
Min. run period
Target 240s ¦ Actual 0s
Set value for minimum running period
·········
Unloaded period
Target 240s ¦ Actual 0s
Set value for unloaded period
8 Initial Start-up
8.6 Control modes
104
User Manual Controller
SIGMA CONTROL 2 SCREW FLUID ≥5.1.2 No.: 9_9450 13 USE