Feature Value
Frequency [MHz] 13.56
Emitted maximum transmitting power at 33 ft dis‐
tance [dB(A)]
11
Tab. 13 RFID
3.1.3 Inputs and outputs with MCSIO
Integrated inputs and outputs with MCSIO type controller
Input/Output Number
Digital input (DI), 24 VDC 8
Digital output transistor (DOT), 24 VDC, 0.5 A 2
Analog input current (AII), 0–20 mA 2
Analog input resistor (AIR), Pt100 2
Digital output relay (DOR), 250 VAC, 4 A 5
Tab. 14 Inputs and outputs with MCSIO
3.1.3.1 Maximum cable lengths
Input/Output Cable length [ft]
Analog input current (AII),
Analog input resistor (AIR)
Analog output current (AOI)
100
Digital input (DI),
Digital output relay (DOR)
330
Digital output transistor (DOT) 100
Tab. 15 Maximum cable lengths
3.1.4 Input/output modules
IOM modules only in combination with the MCS controller type
There are three different types of input/output modules with different numbers of inputs and out‐
puts.
The number of input/output modules actually available depends on the machine type and the avail‐
able options.
Refer to the machine's wiring diagram for the input/output modules installed in your equipment.
Every input/output module is equipped with:
Internal temperature monitoring
Internal low voltage monitoring
LED indication of operational status
3 Technical Data
3.1 Controller SIGMA CONTROL 2
No.: 9_9450 13 USE
User Manual Controller
SIGMA CONTROL 2 SCREW FLUID ≥5.1.2
13

Table of Contents

Other manuals for KAESER SIGMA CONTROL 2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KAESER SIGMA CONTROL 2 and is the answer not in the manual?

KAESER SIGMA CONTROL 2 Specifications

General IconGeneral
Controller TypeMicroprocessor-based
ModelSIGMA CONTROL 2
ManufacturerKAESER
Input Voltage24 V DC
Protection ClassIP54
Communication ProtocolsModbus, Profibus
Data LoggingComprehensive data logging
Remote MonitoringYes
Communication InterfaceEthernet