Feature Value
Frequency [MHz] 13.56
Emitted maximum transmitting power at 33 ft dis‐
tance [dB(A)]
11
Tab. 13 RFID
3.1.3 Inputs and outputs with MCSIO
Integrated inputs and outputs with MCSIO type controller
Input/Output Number
Digital input (DI), 24 VDC 8
Digital output transistor (DOT), 24 VDC, 0.5 A 2
Analog input current (AII), 0–20 mA 2
Analog input resistor (AIR), Pt100 2
Digital output relay (DOR), 250 VAC, 4 A 5
Tab. 14 Inputs and outputs with MCSIO
3.1.3.1 Maximum cable lengths
Input/Output Cable length [ft]
Analog input current (AII),
Analog input resistor (AIR)
Analog output current (AOI)
< 100
Digital input (DI),
Digital output relay (DOR)
< 330
Digital output transistor (DOT) < 100
Tab. 15 Maximum cable lengths
3.1.4 Input/output modules
IOM modules only in combination with the MCS controller type
There are three different types of input/output modules with different numbers of inputs and out‐
puts.
The number of input/output modules actually available depends on the machine type and the avail‐
able options.
Refer to the machine's wiring diagram for the input/output modules installed in your equipment.
Every input/output module is equipped with:
■ Internal temperature monitoring
■ Internal low voltage monitoring
■ LED indication of operational status
3 Technical Data
3.1 Controller SIGMA CONTROL 2
No.: 9_9450 13 USE
User Manual Controller
SIGMA CONTROL 2 SCREW FLUID ≥5.1.2
13