14. Use «Up» or «Down» to set the minutes.
15. Press «Enter».
The date and time for the start of the company shut-down are set.
16. Adjust the date and time for the end of the company shut-down in the same manner.
8 8 p s i 0 8 : 1 5 A M 1 7 6 ° F
Header
5.4.2 Compressor off
Menu
·········
Holidays :
Start : 12/23/22
Date for start
05:00PM
Time for start
End : 01/04/23
Date for end
06:30AM
Time for end
17. Use «Up» or «Down» to select the
Holidays
line.
8 8 p s i 0 8 : 1 5 A M 1 7 6 ° F
Header
5.4.2 Compressor off
Menu
·········
Holidays :
Active line
Start : 12/23/22
Date for start
05:00PM
Time for start
End : 01/04/23
Date for end
06:30AM
Time for end
18. Press «Enter».
The check box
Holidays
will flash.
19. Press «UP».
The check box is activated.
8 8 p s i 0 8 : 1 5 A M 1 7 6 ° F
Header
5.4.2 Compressor off
Menu
·········
Holidays :
Active line with activated check box
Start : 12/23/22
Date for start
05:00PM
Time for start
End : 01/04/23
Date for end
06:30AM
Time for end
20. Press «Enter».
Result In this example, a company shutdown (standstill time) for the time between 12/23/22 / 05:00PM
until 01/04/23 / 06:30AM has been set for the machine.
8.5.3 Controlling the machine remotely (Remote ON/OFF)
If the machine is to be started and stopped from a remotely, the following steps have to be set:
8 Initial Start-up
8.5 Configuring machine start and stop
96
User Manual Controller
SIGMA CONTROL 2 SCREW FLUID ≥5.1.2 No.: 9_9450 13 USE

Table of Contents

Other manuals for KAESER SIGMA CONTROL 2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KAESER SIGMA CONTROL 2 and is the answer not in the manual?

KAESER SIGMA CONTROL 2 Specifications

General IconGeneral
Controller TypeMicroprocessor-based
ModelSIGMA CONTROL 2
ManufacturerKAESER
Input Voltage24 V DC
Protection ClassIP54
Communication ProtocolsModbus, Profibus
Data LoggingComprehensive data logging
Remote MonitoringYes
Communication InterfaceEthernet