8.5.5 Activating/deactivating the idle period “Venting period" function
Prior to the machine's transition from the operating points LOAD to READY you can also activate
an IDLE phase (not with AIRTOWER) ("Venting period" function). The duration of the IDLING
phase can be timed and/or regulated by internal pressure. The machine-dependent venting period
between the LOAD and READY operating modes ensures load changes at minimum material
stresses and is therefore activated at the factory (default setting). If this function is not required,
you can deactivate it.
Precondition Password access level 2 is activated.
1. Select the 5.4.2
<Configuration – Compressor start – Compressor off>
menu.
2. Use «Up» or «Down» to select the
Start
line.
8 8 p s i 0 8 : 1 5 A M 1 7 6 ° F
Header
5.4.2 Compressor off
Menu
Venting period :
Factory setting: "Venting period" function activated
·········
Holidays :
Start : 01/01/22
00:00AM
End : 01/01/22
3. Press «Enter».
The check box
Venting period
will flash.
4. Press «UP».
The check box is deactivated.
8 8 p s i 0 8 : 1 5 A M 1 7 6 ° F
Header
5.4.2 Compressor off
Menu
Venting period :
Active line with deactivated check box
·········
Holidays :
Start : 01/01/22
00:00AM
End : 01/01/22
5. Press «Enter».
The setting is applied.
Apart from the discontinuation of the pressure or load requirement, venting of the machine is also
executed when the «OFF» key is pressed.
Press the «OFF» key twice to immediately shut the machine off.
Press the «OFF» key twice.
Result The machine is switched off without venting (IDLE time).
8.5.6 "Autostart" function
To avoid overloading the main power supply through several machines starting simultaneously a
delay period determining the Autostart of each machine can be entered.
8 Initial Start-up
8.5 Configuring machine start and stop
No.: 9_9450 13 USE
User Manual Controller
SIGMA CONTROL 2 SCREW FLUID ≥5.1.2
99

Table of Contents

Other manuals for KAESER SIGMA CONTROL 2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KAESER SIGMA CONTROL 2 and is the answer not in the manual?

KAESER SIGMA CONTROL 2 Specifications

General IconGeneral
Controller TypeMicroprocessor-based
ModelSIGMA CONTROL 2
ManufacturerKAESER
Input Voltage24 V DC
Protection ClassIP54
Communication ProtocolsModbus, Profibus
Data LoggingComprehensive data logging
Remote MonitoringYes
Communication InterfaceEthernet