3. Activate heat recovery only if the exhaust heat from the machine can be used.
4. Deactivate heat recovery if the exhaust heat from the machine cannot be used.
8.7.1 Activating heat recovery for machine type 2
Heat recovery can be set for local operation, as well as for remote operation. In remote operation,
heat recovery can be controlled by means of a load remote contact.
Example: Heat recovery for machines in "Remote operation".
Precondition Password access level 2 is activated.
1. Open the 5.6
<Configuration – ETM>
menu.
2. Using the «Up» or «Down» key, select the line
Remote mode:
.
8 8 p s i 0 8 : 1 5 A M 1 7 6 ° F
Header
5.6 ETM
Menu
Heat recovery
Local mode:
inactive
Remote mode:
inactive
Active line
current inactive
Heat recovery status
3. Press the «Down» key.
4. Press the «Enter» key.
The currently active operating mode flashes.
5. Use «Up» or «Down» key to set the
active
option.
6. Press the «Enter» key.
The setting is applied accordingly.
8 8 p s i 0 8 : 1 5 A M 1 7 6 ° F
Header
5.6 ETM
Menu
Heat recovery
Local mode:
inactive
Remote mode:
active
Active line
current active
Heat recovery status
8 Initial Start-up
8.7 Electronic Thermal Management
106
User Manual Controller
SIGMA CONTROL 2 SCREW FLUID ≥5.1.2 No.: 9_9450 13 USE

Table of Contents

Other manuals for KAESER SIGMA CONTROL 2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KAESER SIGMA CONTROL 2 and is the answer not in the manual?

KAESER SIGMA CONTROL 2 Specifications

General IconGeneral
Controller TypeMicroprocessor-based
ModelSIGMA CONTROL 2
ManufacturerKAESER
Input Voltage24 V DC
Protection ClassIP54
Communication ProtocolsModbus, Profibus
Data LoggingComprehensive data logging
Remote MonitoringYes
Communication InterfaceEthernet