EasyManuals Logo

KAESER SIGMA CONTROL 2 User Manual

KAESER SIGMA CONTROL 2
246 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #173 background imageLoading...
Page #173 background image
8. Press «Enter».
The output is assigned and activated.
9. Press the «Right» arrow.
10. Press «Enter».
The control field
Logic
flashes.
11. Use «UP» or «Down» to set the desired behavior, see table 75.
12. Press «Enter».
Result For messages at 24 V, the logic is set with the + symbol.
Result The pNloc measured value at the analog AnMod_p_1 input is available as a message and as out‐
put signal at the selected DOR output.
8.11.4 Switching and/or triggering messages with thresholds
Some measured values of the controller can be used for customized messages and/or other
switching functions.
The following measured values are available:
Measured value Explanation Message # Output
System pressure pNloc Threshold for pressure
System pressure pNloc
(lo‐
cal system pressure at compressor output)
0095 O/W/A
Internal pressure pi Threshold for pressure
Internal pressure pi
(internal
pressure pi in the oil separator tank)
0093 O/W/A
ADT Threshold for temperature
ADT
(discharge tempera‐
ture)
0094 O/W/A
Inlet temperature Threshold for temperature
Inlet temperature
(inlet
temperature)
0092 O/W/A
PD temperature Threshold for temperature
PD temperature
(com‐
pressed air discharge temperature)
0096 O/W/A
n Compressor motor
1)
Threshold for the compressor motor speed 0098 O/W/A
1)
Power switching with frequency converter
Tab. 77 Available measured values
Example: Setting for the local network pressure at compressor output
System pressure pNloc
.
Precondition Password access level 2 is activated.
8 Initial Start-up
8.11 Setting input and output signals
No.: 9_9450 13 USE
User Manual Controller
SIGMA CONTROL 2 SCREW FLUID ≥5.1.2
163

Table of Contents

Other manuals for KAESER SIGMA CONTROL 2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KAESER SIGMA CONTROL 2 and is the answer not in the manual?

KAESER SIGMA CONTROL 2 Specifications

General IconGeneral
Controller TypeMicroprocessor-based
ModelSIGMA CONTROL 2
ManufacturerKAESER
Input Voltage24 V DC
Protection ClassIP54
Communication ProtocolsModbus, Profibus
Data LoggingComprehensive data logging
Remote MonitoringYes
Communication InterfaceEthernet