Message Possible cause Remedy
1066 W
AIR%d.0%d - open
circuit
Wire break in line for indicated analog in‐
put.
Check line path and sensor
connection.
1067 W
AIR%d.0%d - sensor
fault
Sensor fault at indicated analog input. Check line path and sensor
connection.
1068 W
AIR%d.0%d - open
circuit
Wire break in line for indicated analog in‐
put.
Check line path and sensor
connection.
1070 W
AIR%d.0%d - accidental
ground
Ground fault in line for ext. sensor at ana‐
log input.
Check line path and sensor
connection.
1071 W
AIR%d.0%d - short-
circuit
Short circuit in line for indicated analog
input.
Check line path and sensor
connection.
1072 W
AIR%d.0%d - open
circuit
Wire break in line for indicated analog in‐
put.
Check line path and sensor
connection.
1073 W
AIR%d.0%d - sensor
fault
Sensor fault at indicated analog input. Check line path and sensor
connection.
1074 W
AIR%d.0%d - open
circuit
Wire break in line for indicated analog in‐
put.
Check line path and sensor
connection.
1076 W
AIR%d.0%d - accidental
ground
Ground fault in line for ext. sensor at ana‐
log input.
Check line path and sensor
connection.
1077 W
AIR%d.0%d - short-
circuit
Short circuit in line for indicated analog
input.
Check line path and sensor
connection.
1078 W
AIR%d.0%d - open
circuit
Wire break in line for indicated analog in‐
put.
Check line path and sensor
connection.
1079 W
AIR%d.0%d - sensor
fault
Sensor fault at indicated analog input. Check line path and sensor
connection.
1080 W
AIR%d.0%d - open
circuit
Wire break in line for indicated analog in‐
put.
Check line path and sensor
connection.
1082 W
AIR%d.0%d - accidental
ground
Ground fault in line for ext. sensor at ana‐
log input.
Check line path and sensor
connection.
1083 W
AIR%d.0%d - short-
circuit
Short circuit in line for indicated analog
input.
Check line path and sensor
connection.
10 Fault Recognition and Rectification
10.3 Interpreting warning messages
No.: 9_9450 13 USE
User Manual Controller
SIGMA CONTROL 2 SCREW FLUID ≥5.1.2
219

Table of Contents

Other manuals for KAESER SIGMA CONTROL 2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KAESER SIGMA CONTROL 2 and is the answer not in the manual?

KAESER SIGMA CONTROL 2 Specifications

General IconGeneral
Controller TypeMicroprocessor-based
ModelSIGMA CONTROL 2
ManufacturerKAESER
Input Voltage24 V DC
Protection ClassIP54
Communication ProtocolsModbus, Profibus
Data LoggingComprehensive data logging
Remote MonitoringYes
Communication InterfaceEthernet