Chapter 10 Online
10-58
Notes
- If the Module Changing Wizard is cancelled, Fault Mask and Skip I/O may be set to protect the
applicable module.
Notes
- If you want to change the module without the Wizard, follow the sequence described below.
[Steps]
1. Set the Skip I/O for the module to change.
2. Set the Fault Mask for the module to change.
3. Remove the module from PLC.
4. Install a new module.
5. Release the Skip I/O for the applicable module.
6. Select [Online]-[PLC Errors/Warnings] to check for any error on the applicable module.
7. If no error found on the applicable module, release the Fault Mask for the module.
- Refer to Skip I/O and Fault Mask for more details on Skip I/O and Fault Mask specified for the module.