Chapter 19 Exclusive Functions for Event Input Module
19-10
19.3 Basic Parameter Setting
Basic parameters of the XGF-SOEA can be set up using the menu or toolbar of the XG5000.
19.3.1 Setting Items
Sets up the method of saving the history occurred in the XGF-SOEA module in the CPU module.
[Sequence]
1) Click on the [Parameter]-[Basic Parameter] in the project tree.
2) Basic operation setting
[Dialog]
[Dialog] description;
a. Overwrite with recent history: used to save the most recent event. If there are more than 3,000 events, the
oldest event is deleted and the new event is saved
b. Maintain the initial history: used to maintain the first event. If there are more than 3,000 events, no new
events will be saved.
a
b