EasyManua.ls Logo

LS Industrial Systems XG5000 - 16.3 Restrictions

LS Industrial Systems XG5000
736 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 16 XG-SIM
16-28
16.3 Restrictions
Comparing to actual PLC, XG-SIM have the following restrictions.
16.3.1 Watchdog Timer
Watchdog timer is installed in XGI PLC to prevent a created PLC program from working abnormally. On the other hand, XG-SIM
executes scan at lower speed than actual XGI series PLC, so the watchdog timer set in the basic parameter does not work properly.
16.3.2 Communication module
XG-SIM does not provide any COM functions. Therefore, the following function blocks created by a program are saved as the internal
data of XG-SIM and they are not actually used for communication.
Class Name Function
Station No. setting P2PSN Designate the station no. of communication counterpart
Reading area designation(BOOL) P2PRD_BOOL Designate the bit data reading area
Reading area designation(BYTE) P2PRD_BYTE Designate the byte data reading area
Reading area designation (WORD) P2PRD_WORD Designate the word data reading area
Reading area designation (DWORD) P2PRD_DWORD Designate the double word reading area
Reading area designation (LWORD) P2PRD_LWORD Designate the long word data reading area
Writing area designation (BOOL) P2PWR_BOOL Designate the bit data writing area
Writing area designation (BYTE) P2PWR_BYTE Designate the byte data writing area
Writing area designation (WORD) P2PWR_WORD Designate the word data writing area
Writing area designation (DWORD) P2PWR_DWORD Designate the double word data writing area
Writing area designation (LWORD) P2PWR_LWORD Designate the long word data writing area

Table of Contents

Related product manuals