Chapter 18 Dedicated XGR Function
18-2
[Dialog box]
[Description of dialog box]
a. Disable the warning message about Single CPU Mode: If Master CPU is operated without standby CPU, the warning message of
redundancy system will be appeared. If it is checked, the warning message will not be appeared. The default value is appearing
warning message.
b. Extended Base Detach Error: When extended base is detached, it decides whether that is considered as error or entire system goes
to initial status and restarts the operation when extended base is attached again. The default value is that entire system goes to initial
status and restarts the operation when extended base is attached again. c. I/Q Base: It synchronizes a data of I/Q Base data. It can set
from the first base to the final base. By checking the box, it determines whether synchronizing I/Q area or not. If it is checked, it
synchronizes from first base to final base. The default value is 0~31 base.
d. M Area: It synchronizes data of M area. It can set from the position of first word to the position of final ward. By checking the box, it
determines whether synchronizing M area or not. If it is checked, it synchronizes from first area to final area. The default value
is %MW0~%MW2000.
e. R Area: It synchronizes data of R area. It can set from the position of first word to the position of final ward. By checking the box, it
determines whether synchronizing R area or not. If it is checked, it synchronizes from first area to final area. The default value
is %RW0~%RW2000.
f. W Area: If R area is set, synchronization area of W are will be define automatically. Initial value is.
g. PID Block: It synchronizes data of PID block. It can set from the first block to final block. By checking the box, it determines whether
synchronizing PID block area or not. If it is checked, it synchronizes from block area to final block area. The default value is 0 block.
h. Default: Initialized to Default setting.
i. OK: Saved the setting value of Run mode and Redundancy synchronization area.
j. Cancel: Cancel the setting value of Run mode and Redundancy synchronization area.