Chapter 19 Exclusive Functions for Event Input Module
19-13
5) With the module selected, click on the [Detail] button.
[Dialog]
[Dialog] description;
Input filter setting: set up the time which enables an event to be identified as an effective input data.
(Setting range: 1ms ~ 100ms)
a. Event history setting
- Overwrite with recent history: use this to save the most recent event.
If the events exceed 300, the oldest event is deleted and the last one is saved.
- Maintain the initial history: use this to retain the first event.
If the events exceed 300, the last one will not be saved.
b. Detail event setting: set up the input condition of the event.
- Type: ‘Rise,’ ‘Fall’ or simultaneously, ‘Rise/Fall’ of event can be set up.
Event conditions can be set up for each input contact point.
- Chatter: abnormal signals not related with event can be processed as chattering.
(Setting range: 2~127)
a
b
c