Learning Basic Features
4.9 Reset and Restart
Reset and restart operations can be setup for inverter operation following a fault trip, based
on the terminal block operation command (if it is configured). When a fault trip occurs, the
inverter cuts off the output and the motor will free-run. Another fault trip may be triggered if
the inverter begins its operation while motor load is in a free-run state.
Group
Code
Name
LCD Display
Parameter Setting
Setting Range
Unit
Operation
drv
Command source
Cmd
Source*
1
2
Fx/Rx-1 or
Fx/Rx-2
05
-
Pr
08
Reset restart setup
RST
Restart
1
Yes
01
09
No. of auto restart
Retry
Number
0
010
10
Auto restart delay
time
Retry Delay
1.0
060
sec
* Displayed under DRV-06 in an LCD keypad.
Note
To prevent a repeat fault trip from occurring, set Cn.71 (speed search options) bit 2 equal to
1. The inverter will perform a speed search at the beginning of the operation.
If the speed search is not enabled, the inverter will start its operation in a normal V/F pattern
and accelerate the motor. If the inverter has been turned on without Reset and Restart
enabled, trips must be reset, then turn the terminal block command off and on to begin the
inverter’s operation.
Use caution when operating the inverter with Power-on Run enabled as the motor will begin
rotating when the inverter starts up.

Table of Contents

Other manuals for LSIS LSLV-S100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LSIS LSLV-S100 and is the answer not in the manual?

LSIS LSLV-S100 Specifications

General IconGeneral
BrandLSIS
ModelLSLV-S100
CategoryController
LanguageEnglish

Related product manuals