Learning Advanced Features
5.5 Safe Operation Mode
When the multi-function terminals are configured to operate in safe mode, operation
commands can be entered in the Safe operation mode only. Safe operation mode is used
to safely and carefully control the inverter through the multi-function terminals.
Safe operation
deceleration time
Px terminal
configuration
Safe Operation Mode Setting Details
From the multi-function terminals, select a terminal to operate in safe
operation mode and set it to 13 (RUN Enable).
Enables safe operation mode.
Recognizes the operation command from a
multi-function input terminal.
Set the operation of the inverter when the multi-function input terminal in
safe operation mode is off.
Blocks the inverter output when the multi-function
terminal is off.
The deceleration time (Q-Stop Time) used in safe
operation mode. It stops after deceleration,
allowing the operation to resume but only after the
operation command is re-entered. The operation
will not begin if only the multi-function terminal is
on.
The inverter decelerates to the deceleration time
(Q-Stop Time) in safe operation mode and stops.
If the multi-function terminal is on, the operation
resumes as soon as the operation command ‘On’
is entered again.
Sets the deceleration time when Ad.71 (Run Dis Stop) is set to 1 (Q-Stop)
or 2 (Q-Stop Resume).