126
Learning Basic Features
Code
Description
bA.09
Time scale
Use the time scale for all time-related values. It is particularly useful when a
more accurate Acc/Dec times are required because of load characteristics,
or when the maximum time range needs to be extended.
Configuration
Description
0
0.01sec
Sets 0.01 second as the minimum unit.
1
0.1sec
Sets 0.1 second as the minimum unit.
2
1sec
Sets 1 second as the minimum unit.
Note that the range of maximum time values may change automatically when the units are
changed. If for example, the acceleration time is set at 6000 seconds, a time scale change from
1 second to 0.01 second will result in a modified acceleration time of 60.00 seconds.
Acc/Dec Time Based on Operation Frequency
Acc/Dec times can be set based on the time required to reach the next step frequency from
the existing operation frequency. To set the Acc/Dec time values based on the existing
operation frequency, set bA. 08 (acc/dec reference) in the Basic group to 1 (Delta Freq).
Group
Code
Name
LCD Display
Parameter Setting
Setting Range
Unit
Operation
ACC
Acceleration
time
Acc Time
20.0
0.0600.0
sec
dEC
Deceleration
time
Dec Time
30.0
0.0600.0
sec
bA
08
Acc/Dec
reference
Ramp T Mode
1
Delta Freq
01
-