Learning Advanced Features
167
Jog Operation 2-Fwd/Rev Jog by Multi-function Terminal
For jog operation 1, an operation command must be entered to start operation, but while
using jog operation 2, a terminal that is set for a forward or reverse jog also starts an
operation. The priorities for frequency, Acc/Dec time and terminal block input during
operation in relation to other operating modes (Dwell, 3-wire, up/down, etc.) are identical to
jog operation 1. If a different operation command is entered during a jog operation, it is
ignored and the operation maintains the jog frequency.
Group
Code
Name
LCD Display
Parameter setting
Setting Range
Unit
dr
11
Jog frequency
JOG Frequency
10.00
0.50-Maximum
frequency
Hz
12
Jog operation
acceleration time
JOG Acc Time
20.00
0.00-600.00
sec
13
Operation
deceleration time
JOG Dec Time
30.00
0.00-600.00
sec
In
65-71
Px terminal
configuration
Px Define
(Px: P1-P7)
46
FWD JOG
-
-
47
REV JOG
Jog Operation by Keypad
Group
Code
Name
LCD Display
Parameter
Setting
Setting
Range
Unit
Dr
90
[ESC] key functions
-
1
JOG
Key
-
-
06
Command source
Cmd
Source*
0
Keypad
-
-
* Displayed under DRV-06 on the LCD keypad.

Table of Contents

Other manuals for LSIS LSLV-S100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LSIS LSLV-S100 and is the answer not in the manual?

LSIS LSLV-S100 Specifications

General IconGeneral
BrandLSIS
ModelLSLV-S100
CategoryController
LanguageEnglish

Related product manuals