Learning Advanced Features
Config Mode Parameter Setting Details
Adjusts LCD brightness/contrast on the LCD keypad.
Check OS version in the inverter and on the LCD keypad.
Checks title version on the LCD keypad.
Checks type of powerboard installed in 1–3 power slot.
Deletes stored trip history.
When inverter SW version is updated and more code is added, CNF-
60 settings will add, display, and operate the added codes. Set CNF-
60 to 1(Yes) and disconnect the LCD keypad from the inverter.
Reconnecting the LCD keypad to the inverter updates titles.
Initialize accumulated electric energy consumption count.
5.30 Timer Settings
Set a multi-function input terminal to a timer and On/Off control the multi-function output and
relay according to the timer settings.
Px terminal
configuration
Timer Setting Details
Choose one of the multi-function input terminals and change it to a timer
terminal by setting it to 38 (Timer In).
OU.31 Relay1,
OU.33 Q1 Define
Set multi-function output terminal or relay to be used as a timer to 28
(Timer out).
OU.55 TimerOn
Delay, OU.56
TimerOff Delay
Input a signal (On) to the timer terminal to operate a timer output (Timer
out) after the time set at OU.55 has passed. When the multi-function input
terminal is off, multi-function output or relay turns off after the time set at
OU.56.