Learning Advanced Features
5.35 Digital Output
Multi-function Output Terminal and Relay Settings
Group
Code
Name
LCD Display
Parameter
Setting
Setting Range
Unit
OU
31
Multi-function relay1
setting
Relay 1
29
Trip
-
-
32*
Multi-function relay2
setting
Relay 2
14
Run
-
-
33
Multi-function output1
setting
Q1 Define
14
Run
-
-
41
Multi-function output
monitor
DO Status
-
00 11
bit
57
Detection frequency
FDT Frequency
30.00
0.00
Maximum
frequency
Hz
58
Detection frequency
band
FDT Band
10.00
In
65
71
Px terminal
configuration
Px Define
16
Exchange
-
-
*Available for 30-75kW models only.
Multi-function Output Terminal and Relay Setting Details
Code
Description
OU.31 Relay1
OU.32 Relay2
Set relay (Relay 1, Relay 2) output options.
OU.33 Q1 Define
Select output options for multi-function output terminal (Q1). Q1 is open
collector TR output.
In.65-71 Px
Define
Set output terminal and relay functions according to OU.57 FDT
(Frequency), OU.58 (FDT Band) settings and fault trip conditions.
Setting
Function
0
None
No output signal.
1
FDT-1
Detects inverter output frequency reaching the user
set frequency. Outputs a signal when the absolute
value (set frequencyoutput frequency) < detected
frequency width/2.
When detected frequency width is 10Hz, FDT-1
output is as shown in the graph below.