Table of Functions
302
8 Table of Functions
This chapter lists all the function settings for S100 series inverter. Set the parameters
required according to the following references. If a set value input is out of range, the
following messages will be displayed on the keyboard. In these cases, the inverter will not
operate with the [ENT] key.
Set value not allocated: rd
Set value repetition (multi-function input, PID reference, PID feedback related): OL
Set value not allowed (select value, V2, I2): no
8.1 Operation Group
The Operation group is used only in the basic keypad mode. It will not be displayed on an
LCD loader.
SL: Sensorless vector control (dr.09) , I IM Sensorless, P PM Sensorless
*O/X: Write-enabled during operation, 7/L/A: Keypad/LCD keypad/Common
Code
Comm.
Address
Name
Keypad
Display
Setting Range
Initial Value
Property*
V/F
SL
Ref.
0h1F00
Target
frequency
0.00
0-Maximum
frequency(Hz)
0.00
O/7
O
I/P
p.7
1
-
0h1F01
Acceleration
time
ACC
0.0-600.0(s)
20.0
O/7
O
I/P
p.1
25
-
0h1F02
Deceleration
time
dEC
0.0-600.0(s)
30.0
O/7
O
I/P
p.1
25
-
0h1F03
Command
source
drv
0
Keypad
1:
Fx/Rx-1
X/7
O
I/P
p.1
17
1
Fx/Rx-1
2
Fx/Rx-2
3
Int 485
4
Field
Bus
1
-
0h1F04
Frequency
reference
source
Frq
0
Keypad-
1
0: Keypad-
1
X/7
O
I/P
p.1
02
1
Keypad-
2
2
V1
4
V2
5
I2
6
Int 485
1
Table of options are provided separately in the option manual.

Table of Contents

Other manuals for LSIS LSLV-S100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LSIS LSLV-S100 and is the answer not in the manual?

LSIS LSLV-S100 Specifications

General IconGeneral
BrandLSIS
ModelLSLV-S100
CategoryController
LanguageEnglish

Related product manuals