LSIS LSLV-S100 - Inverter Memory Control Area Parameter (Read and Write)

LSIS LSLV-S100
469 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
RS-485 Communication Features
299
Comm. Address
Parameter
Scale
Unit
Assigned Content by Bit
Torque Limit
0h0395
Torque Bias
0.1
%
Torque bias
0h0396- 0h399
Reserved
-
-
-
0h039A
Anytime
Para
-
-
Set the CNF.20
*
value (refer to 5.37 Operation
State Monitor on page 246)
0h039B
Monitor
Line-1
-
-
Set the CNF.21
*
value (refer to 5.37 Operation
State Monitor on page 246)
0h039C
Monitor
Line-2
-
-
Set the CNF.22
*
value (refer to 5.37 Operation
State Monitor on page 246)
0h039D
Monitor
Line-3
-
-
Set the CNF.23
*
value (refer to 5.37 Operation
State Monitor on page 246)
* Displayed on an LCD loader only.
Note
A frequency set via communication using the common area frequency address (0h0380,
0h0005) is not saved even when used with the parameter save function. To save a changed
frequency to use after a power cycle, follow these steps:
1 Set dr.07 to 1 (Keypad-1).
2 Set the frequency via communication into the parameter area frequency address (0h1101).
3 Perform the parameter save (0h03E0: '1') before turning off the power. After the power
cycle, the frequency set before turning off the power is displayed.
Inverter Memory Control Area Parameter (Read and Write)
Comm.
Address
Parameter
Scale
Unit
Changeable
During
Operation
Function
0h03E0
Save
parameters
-
-
X
0: No, 1:Yes
0h03E1
Monitor mode
initialization
-
-
O
0: No, 1:Yes
0h03E2
Parameter
initialization
-
-
X
0: No, 1: All Grp, 2: Drv Grp
3: bA Grp, 4: Ad Grp, 5: Cn Grp
6: In Grp, 7: OU Grp, 8: CM Grp
9: AP Grp, 12: Pr Grp, 13: M2
Grp
Setting is prohibited during fault
trip interruptions.
0h03E3
Display changed
-
-
O
0: No, 1: Yes