Learning to Perform Basic Operations
88
[Wiring Diagram] [Operation Pattern]
Note
The instructions in the table are based on the factory default parameter settings. The inverter
may not work correctly if the default parameter settings are changed after the inverter is
purchased. In such cases, initialize all parameters to reset the factory default parameter settings
before following the instructions in the table (refer to 5.23 Parameter Initialization on page 223).
Frequency Setting (Potentiometer) and Operation (Keypad)
Step
Instruction
Keypad Display
1
Turn on the inverter.
-
2
Ensure that the first code of the Operation group is
selected, and the code 0.00 (Command Frequency) is
displayed.
3
Press the [] key 4 times to go to the drv code.
4
Press the [ENT] key.
The drv code in the Operation group is currently set to 1
(Analog Terminal).
5
Press the [] key to change the parameter value to 0
(Keypad), and then press the [ENT] key.
The new parameter value will flash.
6
Press the [ENT] key once again.
The drv code is displayed again. The frequency input
has been configured for the keypad.
7
Press the [] key.
To move to the Frq (Frequency reference source) code.
8
Press the [ENT] key.
The Frq code in the Operation group is set to 0
(Keypad).
0.00
drv
!
)
drv
frq
)