EasyManua.ls Logo

LSIS LSLV-S100 - Troubleshooting Fault Trips

LSIS LSLV-S100
469 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting
384
Keypad
Display
LCD Display
Description
Fan
Exchange
An alarm occurs when the value set at PRT-86 is less than the
value set at PRT-87. To receive fan exchange output signals, set
the digital output terminal or relay (OUT-31 or OUT-33) to 38 (Fan
Exchange).
CAP
Exchange
An alarm occurs when the value set at PRT-63 is less than the
value set at PRT-62 (the value set at PRT-61 must be 2 (Pre
Diag)). To receive CAP exchange signals, set the digital output
terminal or relay (OUT-31 or OUT-33) to 36 (CAP Exchange).
DB
Warn %ED
Displayed when the DB resistor usage rate exceeds the set value.
Set the detection level at Pr.66.
Retry Tr
Tune
Tr tune error warning alarm is activated when Dr.9 is set to 4. The
warning alarm occurs when the motors rotor time constant (Tr) is
either too low or too high.
9.2 Troubleshooting Fault Trips
When a fault trip or warning occurs due to a protection function, refer to the following table
for possible causes and remedies.
Type
Cause
Remedy
Over Load
The load is greater than the motors
rated capacity.
Ensure that the motor and inverter
have appropriate capacity ratings.
The set value for the overload trip level
(Pr.21) is too low.
Increase the set value for the overload
trip level.
Under Load
There is a motor-load connection
problem.
Replace the motor and inverter with
models with lower capacity.
The set value for underload level (Pr.29,
Pr.30) is less than the systems minimum
load.
Reduce the set value for the
underload level.
Over
Current1
Acc/Dec time is too short, compared to
load inertia (GD2).
Increase Acc/Dec time.
The inverter load is greater than the
rated capacity.
Replace the inverter with a model that
has increased capacity.
The inverter supplied an output while the
motor was idling.
Operate the inverter after the motor
has stopped or use the speed search
function (Cn.60).
The mechanical brake of the motor is
operating too fast.
Check the mechanical brake.
Over Voltage
Deceleration time is too short for the load
inertia (GD2).
Increase the acceleration time.
A generative load occurs at the inverter
output.
Use the braking unit.
The input voltage is too high.
Determine if the input voltage is above
the specified value.
eran
ecap
dbw
trer

Table of Contents

Other manuals for LSIS LSLV-S100

Related product manuals